(1)电源系统
DCS系统的供电系统是其运行的基础,电源负荷不要超过60%,以免电源高负荷运行。同时要考虑用的电源,一般采用UPS电源,采用两台UPS互为备用好,一台出现故障后备用机能够无扰切换,提高电源的可靠性。UPS输入电源不要采用电气的同一母线,要根据电气厂用接线取可靠性高的不同母线段电源,这样保证电气一段母线出现问题后不会影响DCS系统的电源。
DCS电源系统(UPS、电源柜等)在现场安装时要安装在满足无尘、无振动、防腐等要求的电子设备间内,同时安装完毕通电前把电缆孔封堵,以防泄漏蒸汽从电缆孔进入电源系统造成电源短路。在DCS电源上电后,要在UPS、电源柜等设备上挂“设备带电运行禁止操作”标识牌,更不准可以在DCS电源系统上接入与DCS系统
无关的负载,如检修电源、检修照明、充电设备、空调等。
(2)冗余系统
现场考虑人们有必要对重要的I/O模块进行冗余,同时考虑操作员站的N:1冗余结构,这样避免由于卡件或操作员站出现硬件故障造成设备停运。
(3)采用后备措施
①手动后备
对于重要的控制回路,可以采用手动后备的方法来提高可靠性。一旦自动控制失灵,用手动操作站直接进行操作,在这种情况下,手动操作站直接输出4~20mA或1~5V的模拟量信号去控制执行机构或直接接地进行设备的操作,可以手动控制生产过程。
②自动后备
自动后备是采用冗余的方式设置另外一套或几套备用控制装置。当处于运行状态的自动控制装置发生故障时,备用控制装置自动投入,维持系统的自动控制。自动后备是冗余系统的一种形式,冗余有主控单元冗余、电源系统冗余、网络冗余、I/O模块冗余、操作员站冗余、服务器冗余等。运行设备出现故障时,热备设备会自动无扰的运行,同时不影响对故障设备的检修。
英文产品详细信息
(1) Power system
The power supply system of the DCS system is the foundation of its operation, and the power load should not exceed 60% to avoid high load operation of the power supply. At the same time, it is necessary to consider using high-quality power supply, generally using UPS power supply. It is best to use two UPS as backup for each other, and one backup machine can switch without disturbance in case of a fault, improving the reliability of the power supply. The UPS input power supply should not use the same electrical busbar. It is necessary to choose different bus section power supplies with high reliability according to the electrical factory wiring, so as to ensure that the power supply of the DCS system will not be affected if there is a problem with the electrical busbar section.
When installing the DCS power supply system (UPS, power cabinet, etc.) on site, it should be installed in an electronic equipment room that meets the requirements of dust-free, vibration free, and anti-corrosion. At the same time, after installation, the cable holes should be sealed before power on to prevent leakage steam from entering the power supply system through the cable holes and causing power short circuits. After powering on the DCS power supply, a "No operation allowed for live operation of equipment" sign should be hung on equipment such as UPS and power cabinet, and it is not allowed to connect loads unrelated to the DCS system, such as maintenance power supply, lighting, charging equipment, air conditioning, etc., to the DCS power supply system.
(2) Redundant system
On site, it is necessary to consider the redundancy of important I/O modules, while also considering the N: 1 redundancy structure of the operator station, in order to avoid equipment shutdown caused by hardware failures of cards or operator stations.
(3) Adopting backup measures
① Manual backup
For important control circuits, manual backup methods can be used to improve reliability. Once the automatic control fails, the manual operation station can be used for direct operation. In this case, the manual operation station can directly output 4-20mA or 1-5V analog signals to control the actuator or directly ground the equipment for operation, which can manually control the production process.
② Automatic backup
Automatic backup is the use of redundancy to set up another set or several sets of backup control devices. When the automatic control device in operation malfunctions, the backup control device automatically switches on to maintain automatic control of the system. Automatic backup is a form of redundant system, which includes redundancy in the main control unit, power supply system, network, I/O module, operator station, and server. When there is a malfunction in the operating equipment, the hot standby equipment will automatically operate undisturbed without affecting the maintenance of the faulty equipment.
免责声明:
AMIKON我们销售新产品和停产产品,独立渠道购买此类特色产品。阿米控不是本网站特色产品的授权分销商、经销商或代表。本网站上使用的所有产品名称/产品图片、商标、品牌和徽标均为其各自所有者的财产。带有这些名称,图片、商标、品牌和徽标的产品描述、描写或销售仅用于识别目的,并不表示与任何权利持有人有任何关联或授权。
YOKOGAWA | AAI141-S00 S2 | EPRO | PR6423/011-131 CON031 |
YOKOGAWA | AAI141-S00 S2 | EPRO | PR6423/012-010 CON021 |
YOKOGAWA | AAI141-S00 S2 | EPRO | PR6426/000-121 CON031 |
YOKOGAWA | AAI143-H00 S1 | EPRO | PR6423/013-020 CON021 |
YOKOGAWA | AAI143-H00 S1 | EPRO | PR6423/013-130 CON021 |
YOKOGAWA | AAI143-S00 S1 | EPRO | PR6423/013-130 CON021 |
YOKOGAWA | AAI143-S00 S1 | EPRO | PR6423/014-010 CON021 |
YOKOGAWA | AAI143-S03 S1 | EPRO | PR6423/015-030 CON021 |
YOKOGAWA | AAI143-S50 S1 | EPRO | PR6423/015-110 CON021 |
YOKOGAWA | AAI543-H00 S1 | EPRO | PR6423/015-111 CON041 |